Refrigeration Design Considerations for Produce Storage Facilities
A produce storage room has two jobs: remove field heat quickly, then hold the product at a steady temperature and humidity until it ships. Many design problems come from treating those two jobs as one.
For Michigan growers and packers, the design has to fit the crop, the harvest volume and the way product moves through the building.
What Should a Produce Storage Refrigeration System Do?
A well-designed system should cool incoming product to its storage temperature in the planned time, hold that temperature evenly across the room, keep humidity in the right range for the crop, and do this without drying or freezing the product near the coils.
Separate Precooling From Storage
Field heat has to come out fast. Cherries, sweet corn and asparagus lose quality quickly if they sit warm after harvest. Precooling with hydrocooling or forced-air cooling removes that heat before product goes into storage.
A storage room can pull product down slowly, but it is usually not designed to do the work of a precooler. Loading warm product into a holding room raises the room temperature and affects everything already stored there.
Size for Pulldown and Holding Loads
The refrigeration load changes through the season:
- Pulldown load: heat from incoming product during harvest, often the largest load
- Holding load: heat through walls, roof and floor, plus fans, lights and people
- Respiration heat: produce keeps giving off heat while it is stored
- Infiltration: warm, moist air that enters through doors during loading
Sizing only for the holding load leaves the system short during harvest. Sizing only for peak pulldown can leave equipment oversized for most of the year. Multiple compressors or variable-speed equipment help match capacity to the load.
Airflow and Temperature Uniformity
Even temperature depends on air reaching every pallet. Stacking patterns, spacing from walls, and the throw of the evaporator fans all matter. Warm spots usually appear where air cannot move through the stack.
Humidity and Coil Selection
Most fresh produce stores best at high relative humidity. A large difference between the coil temperature and the room temperature removes moisture from the air, and that moisture comes out of the product. Evaporators with more surface area can run closer to room temperature and dry the product less. Some crops, such as onions, need drier storage, so the design has to start from the crop.
Doors, Traffic and the Building Envelope
Door openings and gaps in the envelope let warm, moist air into the room. Features that limit it include:
- Insulated panels and a sealed floor perimeter
- Fast-acting doors or strip curtains at high-traffic openings
- Vestibules or staging areas where loading is frequent
- Vapor barriers that keep moisture out of insulation
Controls and Monitoring
Controls hold the room at setpoint, manage defrost, and stage compressors to match the load. Temperature and humidity monitoring with alarms gives you time to respond before a fault damages stored product.
Efficiency belongs in the design from the start. We cover practical options in enhancing energy efficiency in agricultural refrigeration systems. It is also worth knowing the signs of a failing refrigeration system so small problems do not reach the product.
Start the Design From the Crop and the Harvest Rate
Good produce storage design starts with the crop, the harvest rate and the flow of product through the building. Equipment selection comes after those are clear. See our produce and agricultural storage services for the systems we design and install.
If you are planning a new or expanded storage facility in West Michigan, contact RMS Pros before the next harvest season.